kW to Amps Calculator (AC, DC, 3-Phase)

Convert kilowatts to current using voltage and the chosen circuit model.

Circuit

1.5 kilowatts at 120 volts, single-phase, draws 12.5 amps. One kilowatt is 1000 watts. The current then follows the same watts-to-amps formulas used on this site.

CurrentAMPS
12.5 A

Calculated current

Show steps
Kilowatts
1.5 kW
Volts
120 V
Circuit
Single-phase AC
Power factor
1
  1. Circuit is single-phase AC.
  2. Watts = 1.5 × 1000 = 1500 W.
  3. Current = 1500 / (120 × 1) = 12.5 A.

Estimate only. Check equipment labels and local code.

How the number is made

How to use this calculator

  1. Type the kilowatts and the volts.
  2. Choose DC, single-phase AC, or three-phase AC.
  3. For AC, set the power factor.
  4. The current appears in the result card, with the steps beside it.
  5. Submit the form if JavaScript is off. The same formulas run on the server, so the first number is already on the page.

One kilowatt is 1000 watts. The first step always makes that product. The rest of the working is the same as watts to amps . Use this page when a heater, a generator, or an inverter lists kilowatts instead of watts. Do not type 1500 as if it were 1.5 kW. The range on the form stops at 1000 kW, which is already a large industrial figure.

For AC, use RMS voltage and the power factor for the stated operating point. Power factor is real power divided by apparent power; it is not efficiency. The three-phase model assumes a balanced load and uses line-to-line voltage and line current. A power factor of 1 is an explicit example assumption, not an estimate for an unknown load.

Formula

First: P = kW × 1000

P=kW×1000

P is real power, V is voltage, I is current, and PF is power factor. For single-phase AC, the DOE Fundamentals Handbook gives P = VRMS × IRMS × PF. For balanced three-phase wye or delta loads, DOE Volume 3 gives P = √3 × VLL × Iline × PF. This calculator solves those relationships using the RMS voltage and current inputs; unbalanced loads are outside the model.

DC

DC: I = P / V

I=PV

Direct current has no power factor. After the kilowatts become watts, the current is watts divided by volts. A 1.5 kW load at 120 V is 12.5 A. The same 1.5 kW at 12 V is 125 A. Lower voltage means higher current. The DC choice ignores whatever power factor is typed in the form, and the steps say so.

Inverter and battery labels sometimes mix kW of output with DC bus voltage. If you type the AC kilowatts and the DC volts, the current is not the AC current and not a battery current you can trust. Keep the voltage on the same side of the inverter as the kilowatts you typed.

Single-phase AC

Single-phase AC: I = P / (V × PF)

I=PV×PF

At a power factor of 1, single-phase amps match the DC formula after converting kilowatts to watts. At 0.8, the calculated current is higher for the same real power and RMS voltage. This is conditional power arithmetic, not a motor-current rating or a wiring recommendation.

Keep the electrical input power and voltage at the same operating point. Entering 120 V for power specified at 240 V doubles the calculated current under otherwise identical assumptions; it does not describe the same equipment operating at a different supply voltage.

Three-phase AC

Three-phase AC: I = P / (√3 × V × PF)

I=P3×V×PF

Three-phase current is lower than single-phase current for the same kilowatts, volts, and power factor, because the square root of 3 is in the denominator. The volts have to be the line-to-line value. If you type the phase-to-neutral voltage by mistake, the amps come out high. This page does not convert 120 V to 208 V for you. Type the voltage you are actually using.

A three-phase generator that lists kW is listing real power. If the same machine also lists kVA, that is apparent power. Do not type the kVA figure in this form. Use kVA to amps for that rating.

Worked example

  1. Type 3 kilowatts, 240 volts, single-phase, power factor 1.
  2. The engine returns 12.5 amps.
  3. The steps are 3 times 1000, then 3000 divided by 240.
  4. Nothing else is added.
  5. Change the power factor to 0.8 and the current rises. Change the circuit to three-phase and type the line-to-line voltage if that is the system you have. The reference table below is the same engine at power factor 1, single-phase, for a set of round kilowatt values. It is not a list of generator nameplates.

Amps at 120 V and 240 V

Single-phase, power factor 1. Every cell is computed by the same function as the result card.

KilowattsAmps at 120 VAmps at 240 V
0.5 4.1667 2.0833
1 8.3333 4.1667
1.5 12.5 6.25
2 16.6667 8.3333
3 25 12.5
5 41.6667 20.8333
7.5 62.5 31.25
10 83.3333 41.6667

Kilowatts and kilovolt-amperes

Kilowatts are real power. Kilovolt-amperes are apparent power on AC; the numerical values match at power factor 1. For steady DC, power is volts times amps. If equipment lists both kW and kVA, keep the ratings distinct. This form starts with electrical real power; it does not convert a mechanical-output rating into electrical input power.

Server-rendered results use the values in the request URL. Shared addresses may remain in browser history and server logs. Do not enter confidential information.

Common questions

How do I convert kW to amps at 240 volts?

Multiply kilowatts by 1000, then divide by 240 for DC, or for single-phase AC at a power factor of 1. If the power factor is lower, divide by 240 times that power factor. The table on this page already did the power-factor-1 case at 120 V and 240 V.

Is 1 kW the same as 1000 watts?

Yes. The first step on every circuit is that product. The rest of the page is the watts-to-amps working already used on this site.

Does power factor change the amps?

Yes on AC. The current is watts divided by volts and then divided again by the power factor. A factor of 1 is the smallest current. DC does not use it.

How do I convert kW to amps for three-phase?

Convert kilowatts to watts, then divide by the square root of 3, then by the line-to-line volts, then by the power factor. Do not use the single-phase formula on a three-phase load.

Does this determine a wire size?

This page does not determine conductor size or overcurrent protection. Its optional DC link is a voltage-drop estimate only; do not use it for AC or ampacity decisions.

Limitations

This is a calculation aid, not a permit.

For DC only, the optional link carries volts and calculated amps into a voltage-drop estimate. Its length and drop target are separate inputs. It does not select conductors or protective devices, and AC results are not carried into that estimate.

Model: steady DC or sinusoidal AC. AC values are RMS; three-phase requires a balanced load, total input watts, line-to-line voltage and line current. Power factor must match the operating condition. Unbalanced loads and distorted waveforms are outside this model. This is arithmetic, not installation or equipment-selection advice.

It does not pick a conductor, breaker, or generator from a house load list. For DC only, the optional next link opens an idealized copper voltage-drop estimate; that estimate does not check ampacity or determine a safe installation size. AC conductor design needs a qualified review using applicable requirements. This page does not apply motor starting current, continuous-load rules, or efficiency. A 5 kW output is not a 5 kW input if the machine has losses. The values stay in the page address; search engines should use the clean address.

The address of a filled-in calculation includes the kilowatts, volts, circuit, and power factor. That is useful when you send the working to someone else. Search engines should use the clean address of this tool. A filled-in address points its canonical link at the page with no query. The number on the card is the same either way, because the server computes it before any script runs.

Results are rounded to four decimal places. At single-phase power factor 1, 1.5 kW at 120 volts is 12.5 amps, and 3 kW at 240 volts is also 12.5 amps. The table uses the same rounding. These are reproducible arithmetic examples, not measurements or circuit-design results.

Keep the assumptions with the number. A current without the kilowatts, the voltage, the circuit, and the power factor cannot be checked later. Show steps includes those four items so a printed page still shows them. The print button hides the menu and the form. The steps stay.

Sources

  1. U.S. Department of Energy Fundamentals Handbook, Electrical Science, Volume 4. Accessed 2026-10-29.
  2. U.S. Department of Energy Fundamentals Handbook: Electrical Science, Volume 3. Accessed 2026-10-29.

Cite this page

Wattopedia Editorial Team. kW to Amps Calculator (AC, DC, 3-Phase). https://wattopedia.com/kw-to-amps . Updated 2026-10-28.