How to find the minimum breaker rating
- Enter the load current, or convert electrical input watts using the voltage, system and AC power factor.
- Multiply continuous current by 125%; use 100% for a non-continuous load in this general-load model.
- Choose the smallest listed standard rating at or above that minimum.
For the default 16 A continuous load, the minimum is 20 A and the selected standard rating is 20 A. The selection uses the unrounded minimum.
Common breaker sizes by load
Both result columns use this calculator's rating lookup. The continuous-load column includes the 125% allowance.
| Load (A) | Continuous breaker (A) | Non-continuous breaker (A) |
|---|---|---|
| 10 | 15 | 10 |
| 12 | 15 | 15 |
| 15 | 20 | 15 |
| 16 | 20 | 20 |
| 20 | 25 | 20 |
| 21 | 30 | 25 |
| 24 | 30 | 25 |
| 30 | 40 | 30 |
| 32 | 40 | 35 |
| 40 | 50 | 40 |
| 48 | 60 | 50 |
| 50 | 70 | 50 |
| 60 | 80 | 60 |
| 64 | 80 | 70 |
| 80 | 100 | 80 |
A 10 A result is restricted to uses allowed by NEC 2023 210.23(A). It is not a general-purpose receptacle circuit rating. Check the equipment, adopted edition and local rules.
The continuous minimum
Standard sizes are the inverse-time breaker ratings in NEC 2023 Table 240.6. Fuse-only ratings are not included. When the load is continuous, the minimum rating is the load times 1.25. For 16 amps that product is 20 amps. The smallest standard breaker that is at least 20 amps is 20 amps. The arithmetic and the catalog of sizes land on the same number in this example, which is convenient and not always true. If the product falls between two standard ratings, the breaker is the next rating up, not the one below. Rounding down would leave the minimum unmet. The page shows the minimum first and the selected rating second so you can see that step. Mark the load continuous only when it is. A load that is not continuous uses the load amps as the minimum, with no 1.25 factor. Using the factor on a noncontinuous load sizes the breaker high. Skipping it on a continuous load sizes the breaker low. The switch is part of the input, and the steps repeat which choice they used.
Standard ratings, not a custom number
You cannot order a breaker at the exact minimum when that minimum is not a listed rating. Table 240.6 is the list this page uses, and the 2023 edition is the edition named in the steps. The search walks that list until it finds a rating greater than or equal to the minimum. It stops at the first match. It does not jump to a much larger breaker for comfort, and it does not offer a size that is absent from the table. If no rating in the list covers the minimum, the result says so. Do not fill that gap with a number you prefer. The worked 16 amp case does not hit that gap: 20 amps is in the table and it meets the 20 amp minimum. Other loads on the chart use the same walk. Read the row for the load you have instead of scaling this 16 amp example by feel. A larger load can land on a different standard size even when it is also continuous. Run it. The 125 percent factor is not a suggestion you apply twice. The steps apply it once, then select the rating.
What a breaker rating leaves undone
A 20 amp breaker for a 16 amp continuous load is the overcurrent size, not the conductor size. The wire still has to be chosen for the current, the length, the metal, and the temperature column. Take the load amps to the wire page rather than assuming the breaker number is the wire number. This page also does not know the panel spaces, the available fault current, or whether the equipment listing demands a specific breaker type. It does not size a feeder for a whole dwelling, and it does not add several loads into a service calculation. One load in, one rating out. If the nameplate already states a maximum overcurrent device, follow that listing when it is stricter than this minimum. The calculator will not read the nameplate for you. Type the load amps from it. Buy the rating the steps name, then confirm the panel can accept that frame and that interrupting rating. Those checks sit on the panel label and in the equipment instructions, not in the arithmetic. Read them before you purchase the breaker. Panel labeling, handle ties, and series ratings stay outside this result. A 20 amp breaker that the arithmetic accepts can still be the wrong physical device for the panel in the room, so check the labeling before you buy it. The chart repeats this same walk for other common loads. Read the row that matches the measured amps, and do not treat a nearby row as close enough when the minimum sits between two ratings. The result is a planning figure from Table 240.6. It is not a permit, and it does not authorize a breaker the panel or the equipment does not accept.
Common questions
Why is the minimum equal to the breaker in this example?
Sixteen amps times 1.25 is 20 amps, and 20 amps is a standard rating in NEC 2023 Table 240.6. The smallest listed rating that meets the minimum is therefore 20 amps.
Should every load be multiplied by 1.25?
No. The 1.25 factor is for a continuous load. A load that is not continuous keeps its own amp value as the minimum, and the table is searched from there.
Common questions
What size breaker for a 30 A load?
A continuous 30 A load has a calculated minimum of 37.5 A and rounds up to a 40 A standard rating. A non-continuous 30 A load rounds to 30 A in this model.
What size wire for a 20 A circuit?
A breaker rating alone cannot determine the wire. Use the wire size calculator to check both ampacity and voltage drop for the material, terminal rating and run. If verified ampacity data is unavailable, no conductor recommendation is made.
Why use 125% for a continuous load?
The selected general-load assumption reserves capacity for a load running at maximum current for three hours or more. 16 A × 125% = 20 A. Equipment-specific rules and listed 100%-rated assemblies can require a different analysis.
Limitations
This selects a standard current rating for the entered general load. It does not verify conductor protection, available fault current, breaker interrupt rating, equipment listing, coordination, ambient conditions or local adoption. Motors, HVAC, EV charging, mixed loads and other specialized circuits need their applicable rules and manufacturer instructions.
The rating basis is identified below. NEC 2026 has not been verified for this lookup.
Sources
- NFPA 70 Table 240.6(A). NEC 2023 development record; Table 240.6(A). Checked .
- NFPA committee confirmation of the accepted 10 A addition.
- NFPA branch-circuit restrictions for 10 A.
Cite this page
Wattopedia Editorial Team. Breaker Size Calculator. https://wattopedia.com/breaker-size-calculator . Updated 2026-10-29.