Use resistivity for the condition you mean
The input resistivity is a material property with units of ohm metres. This calculator intentionally provides no copper, aluminium, or alloy preset. Values can depend on material composition, manufacturing, and temperature, so a generic entry could look authoritative while not matching the conductor in front of you. Use a traceable value from the exact manufacturer's documentation or a reliable reference that states its conditions. Record the source and temperature associated with that value. If you cannot establish an appropriate resistivity, do not treat a guessed number as a verified cable result. This tool only performs the equation after you provide the physical-property input.
The uniform-conductor model
For a uniform cylindrical conductor, the ideal DC relationship is R = ρL/A. Here ρ is resistivity, L is the length of the conductor included in the path, and A is its cross-sectional area. The calculator normalizes these values to ohm metres, metres, and square metres before calculating ohms. This equation captures the basic relationship that a longer path raises resistance and a larger cross section lowers it. The source describes the same model for a uniform conductor. Real wiring can include terminals, splices, changing geometry, and material variation. Those details are outside the simple equation and are not silently represented in the displayed value.
Choose one-way or round-trip length
Enter the route distance once, then select the conductor path that matches your question. One-way mode includes only the entered conductor length. Round-trip mode doubles that route to represent an outgoing conductor and a return conductor of equal length and properties. This selection matters because resistance scales with total conductor length. It does not account for separate return paths with different material, size, or routing. If the outgoing and return conductors differ, this single-path tool cannot model them accurately. Treat the selected path as an explicit assumption and verify it against the actual circuit diagram before using the estimate.
Read the result with its normalized inputs
The result is an ideal resistance in ohms for the entered resistivity and geometry. The details panel shows normalized length, area, and resistivity so you can inspect the unit conversions. A result that differs by a large factor often points to a length or area unit mismatch. Area units are squared units, so converting them as though they were linear length would be wrong. Recheck every label and the one-way versus round-trip selection. The calculated value is not a measured resistance and includes no measurement uncertainty. For an installed circuit, an appropriate instrument and method may be needed to establish actual conductor and connection resistance.
Temperature and frequency are not modelled
Resistivity can vary with temperature, while the wire's dimensions can also change. The engine uses the single resistivity value you provide and applies it without temperature correction. It does not estimate a conductor's operating temperature. At AC frequencies, skin effect and proximity effects can alter effective resistance, and inductance or other circuit behaviour may matter. This page does not calculate those effects. Use a model and source that match the conductor construction, frequency, and operating condition when those effects are important. Do not interpret the DC result as a complete cable impedance or as a thermal prediction.
Do not infer voltage drop or compliance
Voltage drop depends on current and on the electrical conditions of the circuit, not resistance alone. A complete estimate may require current, supply and load conditions, AC phase relationships, conductor temperature, connection losses, and the applicable calculation method. Ampacity is a separate thermal and regulatory question. The result on this page therefore makes no pass/fail statement and recommends no wire size. Use the appropriate dedicated calculation and authoritative local requirements for installation decisions. For work involving mains wiring or protective devices, consult a qualified professional and the governing code. This calculator is an educational arithmetic aid, not an instruction to install or modify wiring.
Check model suitability before using the estimate
This equation is best understood as a baseline for a uniform conductor with known resistivity, known cross section, and defined path length. It does not model joints, corrosion, strand lay, parallel conductors, temperature rise, insulation, surrounding materials, or a complete return network. It can still help compare how the entered variables affect ideal resistance when their definitions are controlled. Keep the original inputs and their sources with the output. If the question requires a real circuit answer, identify the missing parameters first and use manufacturer data or a recognized engineering method rather than adding an undocumented correction factor.
Worked examples
| Resistivity | Length | Length Unit | Area | Area Unit | Path | Result |
|---|---|---|---|---|---|---|
| 1 | 1 | m | 1 | mm2 | one_way | 1000000 Ω |
| 1 | 1 | m | 1 | mm2 | round_trip | 2000000 Ω |
| 1.0E-6 | 1 | m | 1 | mm2 | one_way | 1 Ω |
| 1.0E-6 | 1 | m | 1 | mm2 | round_trip | 2 Ω |
| 1.0E-6 | 10 | m | 2 | mm2 | one_way | 5 Ω |
Common questions
What formula does the calculator use?
For a uniform conductor it uses R = ρL/A, with resistivity in Ω·m, length in metres, and cross-sectional area in square metres.
Does round-trip mode double the route?
Yes. It models equal outgoing and return conductor lengths by doubling the entered one-way distance.
Does this calculator tell me the correct wire size?
No. It does not calculate ampacity, voltage drop, code compliance, or a recommended wire size.
Limitations
Results use the stated inputs and displayed assumptions.
Enter cross-sectional area, not a safety rating
The area field asks for geometric cross-sectional area in square millimetres or square centimetres. It does not accept a wire gauge directly. Gauge-to-area conversion is a separate task and requires the relevant gauge system and source definition. Even a correct area does not determine the conductor's allowable current. Ampacity and code sizing depend on installation, insulation temperature limits, ambient conditions, bundling, terminations, protection, and jurisdiction-specific rules. A resistance calculation cannot replace those checks. If your area comes from a catalogue, confirm that it describes the conductor itself and not a jacketed cable dimension or nominal outside diameter.
Sources
- OpenStax University Physics Volume 2, §9.3 Resistivity and Resistance
- NIST Guide to the SI, SP 811, Appendix B.8: Factors for Units Listed Alphabetically