How to use this calculator
- Enter the load current, or input power with voltage and AC power factor.
- Choose DC, single-phase or balanced three-phase. Use line-to-line voltage for three-phase.
- Enter the one-way run length and select the conductor material and marked terminal rating.
- Choose the duty and voltage-drop limit, then calculate.
Two checks, one conductor
The load ampacity check includes the continuous-load factor and the applicable small-conductor protection limits. The voltage-drop check compares each verified conductor with the entered target. The selected conductor must meet both conditions; a short cable does not make an undersized conductor acceptable.
Formula
Drop = 2 × one-way length × current × resistance for DC and single-phase. Use √3 instead of 2 for balanced three-phase.
Length and resistance must use matching units. The resistance values used here are a 75 °C resistive model, not a full AC impedance or operating-temperature calculation.
DC examples at 12, 24 and 48 volts
These compare the same fixed 10 AWG copper conductor, 20 A load and 10 ft one-way run. They do not select a conductor or establish its current rating.
| Supply | Calculated drop | Drop percentage |
|---|---|---|
| 12 V DC | 0.4859 V | 4.049% |
| 24 V DC | 0.4859 V | 2.0245% |
| 48 V DC | 0.4859 V | 1.0122% |
Common questions
Can a short run use a smaller wire than the ampacity check allows?
No. The conductor must satisfy both checks. Voltage drop alone cannot establish its allowed current.
Does a 20 A circuit always use the same wire?
No. Duty, conductor material, terminal ratings, length, ambient temperature and installation conditions matter. Follow the equipment instructions and applicable requirements.
Ampacity at the default
Table 310.16 values used here are for 30 C ambient and not more than 3 current-carrying conductors. No other correction is applied. Required ampacity for the default is 30 amps. The load is not continuous, so no 125 percent factor is applied. 10 AWG copper at 75 C is listed at 35 amps. That table cell is not the last word for this size. NEC 240.4(D) limits 10 AWG copper to 30 amps of overcurrent protection, so the usable ampacity is 30 amps. The conductor can carry the 30 amp load on ampacity, and the overcurrent device for that size stops at the same 30 amps. If you change the metal or the temperature column, the listed ampacity changes and this 35 amp cell no longer applies. The page states the column it used. Do not borrow a 75 C copper number for an aluminum conductor or for a 60 C terminal if that is what the equipment requires. The calculator will rerun the table when you change those inputs.
Voltage drop can step the size up
Ampacity said 10 AWG was enough for 30 amps. Voltage drop on 10 AWG over 50 feet at 30 amps is 3.72 volts, which is 3.1 percent of 120 volts. The informational note uses 3 percent, so the size steps up to 8 AWG. Voltage drop on 8 AWG for the same run is 2.334 volts, 1.945 percent. The result to use is 8 AWG. The bump is not because the 10 AWG copper was short on ampacity. It is because the drop on that length was over the note. A shorter run can stay on the ampacity size. A longer run can step up again. Fifty feet is the default length, not a rule for every building. Enter the one-way length of the circuit you are planning. The drop math uses that length, the current, the voltage, and the conductor size. It does not know about poor terminations or extra bends. If the note cannot be met inside the table, the steps say so instead of inventing a size past the table.
Copper, aluminum, and what is left out
Copper and aluminum use different rows of the same table. The default result is copper. An aluminum conductor that must carry the same 30 amps will not automatically be 8 AWG, so you have to select aluminum and read the new steps. The temperature column has to match the terminations. This run uses 75 C. The page does not apply extra ambient correction above 30 C, and it does not apply extra conductor-count correction above 3 current-carrying conductors. If your raceway is hotter or more filled, the usable ampacity falls and the size from this default is no longer the one to install. Continuous loads are a separate switch. This default is not continuous, which is why the 125 percent factor is absent. Turn that on only when the load is continuous, then read the required ampacity again before you trust the size. The chart repeats the same ampacity and drop checks at other currents. A row at another current is not a shortcut back to 8 AWG. Change the inputs and read the new size. Terminations and conduit fill are still corrections you apply yourself, because this page stops at the base table and the informational drop note. The 50 foot default is a sample length, not the length of the building. If the steps say no size in the table can meet the drop, believe that sentence and do not pick a conductor the table did not offer. The result is a planning size with the assumptions printed beside it. It is not a permit, and it does not replace the equipment listing or the adopted code.
Common questions
Why did 10 AWG become 8 AWG?
10 AWG copper at 75 C met the 30 amp ampacity after the NEC 240.4(D) limit. Over 50 feet at 30 amps the drop was 3.72 volts, or 3.1 percent, which is over the 3 percent note. 8 AWG brings the drop to 2.334 volts, 1.945 percent.
Does the table already include every derating?
No. These Table 310.16 values are for 30 C ambient and not more than 3 current-carrying conductors. A hotter room or a fuller raceway needs more correction than this page applies.
Limitations
The ampacity model is limited to the exact source conditions: no more than three current-carrying conductors and 30 °C ambient. It does not apply installation-specific derating, cable restrictions, parallel conductors, motor rules, connections or AC reactance. Resistance rises as the conductor heats. Missing or unverified table rows are never treated as usable conductor ratings.
Sources
- NBS Handbook 100, Table 5: standard annealed copper resistance at 20 C (1966). Checked 2026-11-19.
- Manufacturer copper wire reference facts (Cerrowire and Southwire) (Cerrowire 2017-based reference; Southwire SPEC10000 revision 1.000.113 (2023-based)). Checked 2026-11-19.
- Southwire copper conductor product specifications (revision 1.000.113). Checked 2026-11-19.
Cite this page
Wattopedia Editorial Team. Wire Size Calculator. https://wattopedia.com/wire-size-calculator . Updated 2026-10-29.