Estimate battery amp-hours for a load, duration, discharge depth and efficiency.

A 50 watt load for 24 hours at 12 volts needs 100 amp-hours. Rated energy is 1200 watt-hours.

CapacityPACK
100 Ah

Amp-hours at the typed volts

Show steps
Load
50 W
Hours
24 h
Volts
12 V
Depth of discharge
1
Efficiency
1
Rated energy
1200 Wh
  1. Load energy is watts times hours. Nominal energy is amp-hours times nominal volts; this estimate does not establish usable output.
  2. Energy at the load = 50 × 24 = 1200 Wh.
  3. Rated energy needed = 1200 / (1 × 1) = 1200 Wh.
  4. Amp-hours = 1200 / 12 = 100 Ah.

Estimate only. Check equipment labels and local code.

Ah = W × h / (V × DoD × η)

How to use this calculator

  1. Type the load in watts, the hours you want that load to run, and the nominal pack volts.
  2. Depth of discharge and conversion efficiency start at 1, which means the full rated energy and no conversion loss.
  3. Type a fraction if your datasheet gives one.
  4. The card shows watt-hours at the load, rated watt-hours needed, and amp-hours.
  5. Submit the form if JavaScript is off. The same product runs on the server, so the first number is already on the page.

The default is a hypothetical constant 50 watt load for 24 hours at 12 volts. Load energy is 1200 watt-hours. At depth 1 and efficiency 1, nominal energy needed is 1200 watt-hours, or 100 Ah. This is the inverse of the runtime calculation under identical assumptions, not a laptop rating or a battery performance guarantee. Enter power delivered after the conversion losses represented by the efficiency input. If power is already measured at the battery, use efficiency 1 to avoid counting those losses twice.

The starting fractions of 1 describe full nominal energy and no conversion loss; they are not recommended battery settings. The bound DOE BESS method distinguishes nominal Ah-times-volts energy from measured capacity and efficiency. The bound NIST references support unit relationships, and the Virginia Cooperative Extension factsheet supports energy from power and time. These sources do not select a battery chemistry, discharge limit or product.

Formula

Wh = W × h

rated Wh = Wh / (DoD × η)

Ah = rated Wh / V

Ah = W×h V×DoD×η

DOE BESS evaluation text says rated capacity Erated is often estimated as the amp-hours of the battery multiplied by the nominal voltage. NIST SP 811 lists ampere hour to coulomb as 3.6 times 10 to the 3. One watt-hour is 3600 joules. Amp-hours times volts is therefore watt-hours. This page solves for amp-hours. The runtime page solves for hours. Both pages use the same identity.

The default case

50 times 24 is 1200 watt-hours. 1200 divided by 1 times 1 is 1200 rated watt-hours. 1200 divided by 12 is 100 amp-hours. Type depth 0.5. Rated energy needed doubles to 2400 watt-hours. Amp-hours become 200. Type efficiency 0.9 on the default. Rated energy needed is 1333.3333 watt-hours. Amp-hours are 111.1111. Those last two runs show what the extra boxes do. They are not recommendations.

Type 100 watts for 12 hours at 12.8 volts. Load energy is 1200 watt-hours. Amp-hours are 93.75. A 12.8 volt pack stores more watt-hours per amp-hour than a 12 volt pack. Amp-hours alone do not compare energy. That is why volts stay on the form.

The hours chart below holds a 50 watt, 12 volt, depth 1, efficiency 1 load for 4, 8, 12, 24, and 48 hours. Every cell is this engine. 4 hours is 16.6667 amp-hours. 24 hours is 100 amp-hours. 48 hours is 200 amp-hours.

Worked example

  1. Type 10 watts, 30 hours, and 6 volts.
  2. Load energy is 300 watt-hours.
  3. Amp-hours are 50.
  4. That is the inverse of the runtime example that runs a 50 amp-hour 6 volt pack at 10 watts for 30 hours.
  5. Open the next-step button. Runtime should print 30 hours if you leave depth and efficiency at 1.

Two 12 volt 100 amp-hour batteries in series are 24 volts and 100 amp-hours if they share the series string rating, which is 2400 watt-hours, not 1200. This form models one nominal voltage. If you series or parallel packs, type the resulting volts from the datasheet, then read amp-hours. Do not double amp-hours and volts by guess.

Depth of discharge and efficiency

Depth of discharge on this form is a fraction from greater than 0 through 1. 1 means you size the pack from full rated watt-hours. 0.5 means you count only half of the rated watt-hours as usable, so the pack amp-hours go up. Conversion efficiency is the same kind of fraction. 1 means the load watts are already at the pack. 0.9 means 10 percent is lost in conversion, so more rated watt-hours are needed. Both boxes reject 0 and reject values above 1. There is no chemistry picker.

DOE BESS evaluates measured capacity and efficiency separately from nominal energy. This form solves a conditional nominal-energy model for amp-hours using your stated load, duration and fractions. It does not perform a capacity test or establish cycle life, discharge-rate behavior, a safe discharge limit or an equipment margin.

50 W at 12 V, full rated energy

Depth of discharge 1, efficiency 1. Every cell is this engine.

HoursAmp-hours
4 16.6667
8 33.3333
12 50
24 100
48 200

How this fits the power chain

Runtime estimates duration from nominal amp-hours; this page estimates nominal amp-hours from duration. Opening runtime checks the inverse calculation, not an independent performance measurement. Load-side power after a converter is not battery input power when conversion losses apply, so this result does not establish battery current, conductor ampacity or fuse selection.

A hypothetical 50 watt load for 24 hours at 12 volts is 100 amp-hours under the full-energy, no-loss assumptions. For 8 hours, 50 times 8 is 400 watt-hours; dividing by 12 gives 33.3333 amp-hours. Keep the duration and ideal assumptions attached to both figures rather than treating either as a product recommendation.

Depth 0.5 doubles the nominal energy needed. Efficiency 0.9 raises it by one ninth. Applying both to the 50 watt, 24 hour, 12 volt example gives 1200 divided by 0.45, or 2666.6667 watt-hours and 222.2222 amp-hours. These fractions illustrate the calculation; they are not operating recommendations.

Solar-array energy, charge-controller current and inverter capability require their own supported inputs and methods. The nominal amp-hour estimate here answers none of those equipment-selection questions.

Common questions

What size battery for a 50 watt load overnight?

At 12 volts and 24 hours with full rated energy, 100 amp-hours. Type a shorter night if that is what you have. Type depth below 1 if the datasheet says you must.

Why is depth of discharge 1?

It makes the starting example an ideal calculation from full nominal energy. It is not a recommendation to fully discharge a battery. Use the permitted discharge fraction for the exact equipment and conditions.

Does this include an inverter?

Only if you type efficiency below 1 and the load watts on the AC side. The default 1 is a DC load at the pack.

How is this different from battery runtime?

Runtime starts from amp-hours and finds hours. This page starts from hours and finds amp-hours. The identity is the same.

Is 50 watts a laptop?

No particular laptop is represented. The constant 50 watt load is a hypothetical example; use supported power data for your actual load.

Limitations

This is a calculation aid, not a permit.

Next step: battery runtime

The runtime page repeats these amp-hours, volts, load watts, depth and efficiency. It checks the inverse arithmetic under the same assumptions, not the performance or suitability of a real battery.

This form does not select an inverter, solar array, charge controller, battery model or protective device. It estimates nominal amp-hours from load watts and duration, with voltage and stated fractions. Product selection also needs equipment-specific power, surge, charging and operating limits that this model does not evaluate.

It does not store what you type. Search engines should use the clean address of this tool. It is not a substitute for the capacity test in the battery manual. If the pack cuts off early, the BMS or the load is not the constant watts on this card.

The address of a filled-in calculation includes watts, hours, volts, depth of discharge, and efficiency. A filled-in address points its canonical link at the page with no query. Results are rounded to four decimal places. Keep the assumptions with the number. The print button hides the menu and the form. The steps stay.

For a separate recharge estimate, wall energy = stored energy replenished / charging efficiency, using the same energy units. Replenishing 1.2 kWh at an assumed charging efficiency of 0.8 requires 1.5 kWh from the wall before any separately excluded standby use. Multiply that wall energy by the applicable price per kWh. Charging efficiency is separate from this form's discharge-path conversion efficiency; this page does not calculate recharge cost.

Sources

  1. U.S. Department of Energy Federal Energy Management Program, Battery Energy Storage System Evaluation Method. Accessed 2026-10-17.
  2. NIST Guide to the SI, SP 811, Appendix B.8: conversion factors. Accessed 2026-10-14.
  3. NIST Special Publication 330, The International System of Units (SI), Section 2. Accessed 2026-10-14.
  4. Virginia Cooperative Extension ENERGY SERIES: Estimating Appliance and Home Electronic Energy Use. Accessed 2026-10-19.

The bound DOE BESS method supports nominal Ah-times-volts energy, NIST supports unit relationships, and Virginia Cooperative Extension supports energy from power and time. The hypothetical load and entered fractions do not establish measured capacity or a suitable battery product.

Cite this page

Wattopedia Editorial Team. Battery size. https://wattopedia.com/battery-size-calculator . Updated 2026-11-15.