Wh = Ah × V
How to use this calculator
- Type the battery amp-hour rating, the nominal pack volts, and the load in watts.
- Depth of discharge and conversion efficiency start at 1, which means the full rated energy and no inverter loss.
- Type a fraction if your datasheet gives one.
- The card shows watt-hours, usable watt-hours, and hours of runtime.
- Submit the form if JavaScript is off. The same product runs on the server, so the first number is already on the page.
The default is a hypothetical 100 amp-hour, 12 volt battery with a constant 50 watt load. Nominal energy is 1200 watt-hours. At depth of discharge 1 and efficiency 1, the conditional runtime is 24 hours. The 50 watt input is an example, not a laptop specification. Enter power delivered to the load after the conversion losses represented by the efficiency input. If power is already measured at the battery, use efficiency 1 to avoid counting those losses twice.
The starting fractions of 1 describe full nominal energy and no conversion loss. They are not recommended discharge limits or measured efficiency. The bound DOE BESS evaluation method distinguishes rated energy from measured capacity and efficiency; the bound Victron manual discusses discharge-rate and cutoff conditions. Use documented conditions for the actual battery and load rather than a universal chemistry percentage.
Formula
Wh = Ah × V
usable Wh = Wh × DoD × η
hours = usable Wh / W
DOE BESS evaluation text says rated capacity Erated is often estimated as the amp-hours of the battery multiplied by the nominal voltage. NIST SP 811 lists ampere hour to coulomb as 3.6 times 10 to the 3, which is exact. One watt-hour is 3600 joules. Amp-hours times volts is therefore watt-hours. Runtime at a constant load is energy divided by power. Peukert's law, temperature, and BMS cutoffs are not in this product.
A manufacturer's runtime table may use a particular discharge rate and cutoff voltage. Compare those test conditions with your load before treating this idealized estimate as useful runtime.
The default case
100 times 12 is 1200 watt-hours. 1200 times 1 times 1 is 1200 usable watt-hours. 1200 divided by 50 is 24 hours. Type 100 watts with the same pack. Runtime is 12 hours. The table below holds that 12 volt 100 amp-hour pack at full rated energy for loads from 10 watts to 500 watts. Every cell is this engine.
Type 100 amp-hours, 12.8 volts, and 150 watts. Energy is 1280 watt-hours. Runtime is 8.5333 hours at depth 1 and efficiency 1. Type depth 0.5. Usable energy is 640 watt-hours. Runtime is 4.2667 hours. Type efficiency 0.9 on the 100 amp-hour 12 volt 50 watt default. Usable energy is 1080 watt-hours. Runtime is 21.6 hours. Those last two runs show what the extra boxes do. They are not recommendations.
Worked example
- Type 50 amp-hours, 6 volts, and 10 watts.
- Energy is 300 watt-hours.
- Runtime is 30 hours.
- A 6 volt 50 amp-hour block is a different pack from a 12 volt 50 amp-hour block.
- Amp-hours alone do not compare energy. That is the point of multiplying by volts. Two 12 volt 100 amp-hour batteries in series are 24 volts and 100 amp-hours if they share the series string rating, which is 2400 watt-hours, not 1200. This form models one nominal voltage. If you series or parallel packs, type the resulting amp-hours and volts from the datasheet, not a guess.
A separate current calculation requires power and voltage at the same measurement point. For an ideal DC load with no conversion loss, 50 watts at 12 volts is about 4.1667 amps. If those 50 watts are delivered after a converter, battery-side input power is higher when efficiency is below 1. Runtime hours do not select wiring, fuses or other equipment.
Depth of discharge and efficiency
Depth of discharge on this form is a fraction from greater than 0 through 1. 1 means you count the full rated watt-hours. 0.5 means you count half. Conversion efficiency is the same kind of fraction. 1 means the load watts are already at the pack. 0.9 means 10 percent is lost in conversion, so usable energy is smaller and hours fall. Both boxes reject 0 and reject values above 1. There is no chemistry picker. LFP, NMC, and lead-acid limits belong on the sheet, then in these boxes.
DOE BESS evaluates measured capacity and efficiency separately from the nominal Ah-times-volts estimate. This calculator applies your stated discharge and conversion fractions to nominal energy; it does not perform that metered evaluation or establish cycle life, discharge-rate behavior or a safe operating limit.
12 V, 100 Ah pack at full rated energy
Depth of discharge 1, efficiency 1. Every cell is this engine.
| Load (W) | Runtime (h) |
|---|---|
| 10 | 120 |
| 25 | 48 |
| 50 | 24 |
| 100 | 12 |
| 150 | 8 |
| 200 | 6 |
| 500 | 2.4 |
Inputs needed for a runtime estimate
Start with the battery capacity in amp-hours and the nominal voltage that belongs to that same battery or pack. These values estimate rated energy in watt-hours. Next enter the power draw of the connected load. If you know that only part of rated energy is available for use, enter a depth-of-discharge fraction. If the path from battery to load has a documented efficiency, enter that value as well. The calculator keeps those inputs visible so that a result can be traced back to its assumptions.
Do not copy the capacity from one part of a system and the voltage from another unless the manufacturer confirms that they describe the same pack. A battery may contain cells connected in series or parallel, and product labels can present cell-level and system-level ratings. Use the documented nominal values for the rated assembly. When a manufacturer gives an energy rating directly, retain that value and its test conditions rather than substituting an estimate based on incomplete information.
For the load, use measured or documented power for the operating mode you want to evaluate. A device name alone does not tell the calculator how much energy it draws. A motor may start at a different level from its steady running demand. A refrigerator or pump may cycle. A computer can change its draw with the work it performs. If the load varies, a representative average over the period is more useful for this simple model than a brief peak. Keep the selected load basis with the result so another reader can understand what it represents.
The rated-energy and runtime formulas
The first relationship estimates rated energy: amp-hours multiplied by nominal volts gives watt-hours. The U.S. Department of Energy Federal Energy Management Program describes this as a common estimate for rated battery energy and separately discusses measured capacity and efficiency. The calculator then applies the user-entered usable fraction and efficiency. Its final step divides the adjusted watt-hours by load watts to estimate hours. These steps are dimensional arithmetic, not a measurement of battery health or a prediction validated by a manufacturer.
For an illustrative input, a 100 Ah pack at 12 V gives 1200 Wh of rated energy. With a 50 W constant load, using the full rated-energy value and no loss in the model gives 24 hours. This example shows how the units fit together; it does not describe a specific product or recommend a discharge limit. If a user enters a 0.5 usable fraction, the model uses half of the rated-energy estimate before dividing by the load. If a user enters 0.9 efficiency, the model reduces energy by that entered factor. Neither factor is a universal default. Select them only when product documentation or a clearly stated scenario supports them.
The displayed answer is rounded for readability. Decimal places communicate the calculation's output format, not the accuracy of the capacity label, load estimate, or efficiency assumption. If the input itself is an approximation, the result remains an approximation even when it contains decimal digits. The value should be read together with the full set of inputs and the limitations of the chosen model.
Rated energy is not the same as usable energy
A nameplate capacity is not necessarily the energy that a connected device can draw before shutdown. The product may reserve energy, enforce a minimum state of charge, or stop output at a voltage or temperature threshold. Conversion equipment can also consume energy. Capacity measurements may vary with discharge rate and test endpoint. A monitoring manual explains rate-dependent capacity in its stated example, but that example is not a universal curve for every chemistry or product.
The calculator cannot infer the battery chemistry, age, health, temperature, internal resistance, protection settings, or cutoff behavior from amp-hours. It does not know whether the load is connected directly or through an inverter. It also does not model a changing voltage or changing load unless a future tool explicitly supports those behaviors. Do not interpret a result as a guarantee, runtime rating, or proof that a device and battery are compatible.
When an exact manufacturer document lists usable energy under stated conditions, use that information for product-specific decisions. Keep any assumed usable fraction clearly labeled as an assumption. A conservative estimate is not the same as a validated operating limit. Follow the battery and equipment manuals for charging, discharge, thermal limits, wiring, protection, and approved use. Ask the manufacturer or a qualified professional when system safety or compatibility is uncertain.
How to read and improve the result
Read the answer as hours for the exact inputs shown. If it looks unexpectedly high or low, check the units first. Confirm that capacity is in amp-hours, voltage is in volts, load is in watts, and the fractions are entered as decimals within the accepted range. A unit mismatch can change the result substantially. Check whether a published capacity uses the same nominal voltage and discharge conditions as the values entered.
For a cycling device, measure energy over a representative period when possible, then use average power for that period. If equipment documentation gives a specific power value for the desired mode, keep the mode and measurement basis in your notes. For a battery feeding an inverter, use an efficiency figure documented for that operating point if available. Efficiency can change with load, and one figure may not describe every condition. Do not treat a value from another model as interchangeable.
This page provides an estimate, not a battery test. It does not determine circuit, conductor, fuse, charger, or inverter suitability. It does not choose a safe depth of discharge or establish a backup runtime that can be relied on during an emergency. Those decisions require product-specific ratings and the applicable instructions. Use the battery size calculator when estimating a capacity requirement from a stated load scenario, the inverter current calculator for a separate user-supplied inverter calculation, or browse the battery calculator collection for related tools. Keep the models separate and use each result only for its stated purpose.
Common questions
Can amp-hours alone tell me how long a battery will run?
No. Amp-hours describe charge capacity. Nominal voltage is also needed to estimate rated energy, and the load power is needed to estimate duration. Product limits and usable energy can further change the result.
Is the result guaranteed for my battery?
No. It is conditional arithmetic from values you enter. It does not test a battery or know its chemistry, condition, discharge rate, temperature, cutoff, or protection settings. Check the exact manufacturer's documentation.
Limitations
This is a calculation aid, not a permit.
Load-side watts can differ from battery input watts when a converter has losses. The separate current calculator opens without carrying these values; establish power and voltage at the same point before calculating current.
This runtime model does not select an inverter, solar array, charge controller, battery model or protective device. Those decisions need their own equipment data and operating conditions. The form accepts amp-hours, so 100 milliamp-hours would be entered as 0.1 Ah if the other required inputs are known and within the limits.
It does not store what you type. Search engines should use the clean address of this tool. It is not a substitute for the runtime test in the battery manual. If the pack cuts off early, the BMS or the load is not the constant watts on this card.
The address of a filled-in calculation includes amp-hours, volts, watts, depth of discharge, and efficiency. A filled-in address points its canonical link at the page with no query. Results are rounded to four decimal places. Keep the assumptions with the number. The print button hides the menu and the form. The steps stay.
For a separate recharge estimate, wall energy = stored energy replenished / charging efficiency, using the same energy units. Replenishing 1.2 kWh at an assumed charging efficiency of 0.8 requires 1.5 kWh from the wall before any separately excluded standby use. Multiply that wall energy by the applicable price per kWh. Charging efficiency is separate from this form's discharge-path conversion efficiency; this page does not calculate recharge cost.
Sources
- U.S. Department of Energy Federal Energy Management Program, Battery Energy Storage System Evaluation Method. Accessed 2026-10-17.
- NIST Guide to the SI, SP 811, Appendix B.8: conversion factors. Accessed 2026-10-14.
- Victron BMV-700 manual: battery capacity and Peukert exponent. Accessed 2026-10-14.
The bound DOE BESS method supports the nominal Ah-times-volts energy estimate, NIST supports the unit relationships, and the Victron manual supplies discharge-condition context. None establishes measured runtime for the hypothetical load or recommends a discharge limit.