DC Fuse Size Calculator

A 15 A continuous DC load has a 18.75 A minimum and rounds to a 20 A blade ATC/ATO fuse in the cited product range.

Include the highest charging voltage. The fuse and its holder must both be rated for it.

Check an existing wire (optional)

Leave blank to skip this check. Enter a gauge such as 10 or 1/0.

Calculated minimum 18.75 A (15 A × 125%). Rounded up to 20 A (blade ATC/ATO).

Currentblade ATC/ATO
20 A

Fuse rating (blade ATC/ATO)

Show steps
  1. Calculated minimum = 15 A × 125% = 18.75 A.
  2. The smallest eligible blade ATC/ATO rating at or above the unrounded minimum is 20 A.
  3. Maximum fuse voltage: 32 V DC. Published interrupt rating: 1,000 A at 32 V DC.
  4. ATOF ratings apply to the cited Littelfuse series, not every ATC/ATO-format product.
  5. Ambient temperature, terminals, wire and the holder can require additional derating. The 125% load allowance is not a thermal verification.
  6. The shunt is not a fuse and is excluded.

Minimum size for this load. Local code and the equipment label take priority.

How the DC fuse rating is selected

Multiply continuous current by 125%, then select the smallest eligible rating at or above that unrounded minimum in the chosen manufacturer's range. For the default 15 A load, the minimum is 18.75 A and the listed blade ATC/ATO fuse rating is 20 A.

Common blade ATC/ATO fuse sizes by load

Current (A)Calculated minimum (A)Fuse rating (A)
11.252
56.257.5
1012.515
1518.7520
202525
243030
3037.540
324040

Fuse family limits

These are named product ranges, not universal ratings for every fuse with the same format. The manufacturer's current product sheet and the complete fuse-holder assembly must be checked.

blade ATC/ATO: Littelfuse

32 V DC maximum for the listed fuses. Interrupt rating: 1,000 A at 32 V DC.

  • ATOF ratings apply to the cited Littelfuse series, not every ATC/ATO-format product.
  • Ambient temperature, terminals, wire and the holder can require additional derating. The 125% load allowance is not a thermal verification.
  • The shunt is not a fuse and is excluded.

MIDI: Littelfuse

32 V DC maximum for the listed fuses. Interrupt rating: 2,000 A at 32 V DC.

  • The cited datasheet marks 150 A, 175 A and 200 A versions for short-circuit protection only. They are excluded from this continuous-load selector.
  • Temperature, cable, terminals and holder limits can require additional derating. Verify the manufacturer curve and application.

ANL: Blue Sea Systems

80 V DC maximum for the listed fuses. Interrupt rating: 6,000 A at 80 V DC.

  • The current manufacturer sheets rate these fuses at 80 V DC; the selected holder and complete assembly can have a lower voltage limit.
  • Only the cited products are listed. Other ANL ratings and brands are not inferred.
  • Check the time-current curve, holder, temperature and installation limits. Ignition protection is not claimed for every rating.

MRBF: Blue Sea Systems

58 V DC maximum for the listed fuses. Interrupt rating: 10,000 A at 14 V DC; 5,000 A at 32 V DC; 2,000 A at 58 V DC.

  • Use the manufacturer-specified MRBF terminal fuse block. Never mount the fuse directly on a battery terminal.
  • Interrupt capacity decreases as system voltage increases. Check maximum charging voltage and available battery fault current.
  • Check holder, terminal, cable and ambient-temperature limits; a current match alone does not verify the installation.

Class T: Blue Sea Systems

125 V DC maximum for the listed fuses. Interrupt rating: 20,000 A at 125 V DC.

  • Use the fuse holder specified for the exact product; the two physical size ranges use different holders.
  • Only these Blue Sea products are covered, not all Class T manufacturers or ratings.
  • Check the time-current curve, holder continuous-current rating, ambient temperature and battery fault current.

Common questions

What fuse for a 20 A continuous DC load?

The calculated minimum is 25 A. The cited blade range includes a 25 A fuse. Other formats can round to a different rating.

Why are some MIDI ratings excluded?

The cited datasheet marks 150 A, 175 A and 200 A versions for short-circuit protection only. They are excluded from this continuous-load selector.

Does a matching current rating finish the selection?

No. Confirm the voltage rating of both fuse and holder, available fault current versus interrupt rating, wire protection, inrush, temperature, mounting and equipment instructions. A 125% allowance does not replace the manufacturer's thermal derating guidance.

Can I disable the continuous-load allowance?

This tool is for continuous DC loads, so the allowance always applies. Older saved links containing a continuous setting use the same 125% calculation.

Limitations

The result is a minimum current-rating lookup, not verification of a complete DC protection system. Wire ampacity is checked only when a gauge is entered and verified, authorized source data exists. Temperature corrections, holder limits, inrush and fault-current adequacy still need application-specific review.

Sources

  1. Littelfuse: ATOF series 287 datasheet, Ratings and Specifications. Revised 02/04/2025 (manufacturer date notation). Checked .
  2. Littelfuse: MIDI 32 V bolt-down datasheet, pages 1-2, Ratings footnote 1. Revised 07/01/2024 (manufacturer date notation). Checked .
  3. Blue Sea Systems: ANL individual manufacturer specification sheets. Undated web specifications, checked 18 Nov 2026. Checked .
    Individual rating specification sheets
  4. Blue Sea Systems: MRBF individual manufacturer specification sheets. Undated web specifications, checked 18 Nov 2026. Checked .
    Individual rating specification sheets
  5. Blue Sea Systems: Class T individual manufacturer specification sheets. Undated web specifications, checked 18 Nov 2026. Checked .
    Individual rating specification sheets