Storage = daily kWh × days / (DoD × η)
How to use this calculator
- Type daily energy in kilowatt-hours.
- Type days of autonomy.
- Type depth of discharge and efficiency from greater than 0 through 1.
- Leave both at 1 if you do not have datasheet fractions.
- The card returns rated storage kilowatt-hours. Submit the form if JavaScript is off. The same quotient runs on the server, so the first number is already on the page.
The default is 12 kWh for 1 day at depth 1 and efficiency 1. Storage equals 12 kWh. The 12 kWh daily-energy input is an illustrative scenario, not a household estimate or an appliance claim. Depth 1 and efficiency 1 mean this calculation applies no usable-capacity or conversion derating. This page does not store 80 percent DoD. Type 0.8 if a product sheet supports that usable fraction. Then storage is 15 kWh.
The DOE Energy Storage Handbook treats usable energy as rated energy times usable fraction and conversion efficiency. This page inverts that: rated energy is daily energy times days, divided by those fractions. Battery size in amp-hours does the same inversion at a typed voltage. Use amp-hours when you think in 12 V banks. Use this page when you think in kilowatt-hours.
Formula
kWh_rated = (kWh_day × days) / (DoD × η)
Daily energy must be from 0.1 through 500 kWh. Days must be from 0.1 through 30. Depth and efficiency must be greater than 0 through 1. Two days at the default is 24 kWh. Seven days is 84 kWh. Efficiency 0.9 at one day is 13.3333 kWh. Those rows are this engine, not a vendor 80 percent table.
The default case
12 kWh. Next step carries 1000 W, 12 hours, 12 V, depth 1, and efficiency 1 into battery size, which is 12 kWh as amp-hours at 12 V: 1000 Ah. That pairing keeps energy equal. A separate hypothetical 1500 W load running for 8 hours also uses 12 kWh; it is not identified here as a typical toaster-oven rating.
Worked example
- You want two cloudy days of the 12 kWh load.
- Type 12, 2, 1, and 1.
- The card prints 24 kWh.
- If the lithium sheet says 0.9 round-trip and 0.9 depth, type those. 12 × 2 / (0.9 × 0.9) is 29.6296 kWh.
- Do not also multiply by 1.25. A 1.25 would be a second hidden margin, the same class of guess this site refused on generator and inverter size.
A 746 W load for 8 hours is 5.968 kWh. One day at DoD 1 is 5.968 kWh of storage. At 12 V that is 497.3333 Ah on the amp-hour page. HP to kW still does not size batteries. Bring energy here after you know watt-hours.
Days of autonomy at 12 kWh
Each row is this engine at 12 kWh, depth 1, and efficiency 1.
| Days | Storage kWh |
|---|---|
| 1 | 12 |
| 2 | 24 |
| 3 | 36 |
| 4 | 48 |
| 7 | 84 |
How this fits the power chain
Solar panel size is array kilowatts. This page is storage energy. Battery runtime is hours from a pack you already have. Inverter size is VA for the AC load. Peak sun hours are GHI. A 12 kWh battery is not a 12 kW array and not a 12 kVA inverter.
If the load is 1500 W at 120 V, watts to amps is 12.5 A. DC current at 12 V for the same 1500 W at eta 1 is 125 A. Cable the DC side for that current, not for 12.5 A. This storage page does not print amps. Keep AC and DC currents on their own tools.
Generator size remains the backup if the battery is empty. NEC 702.4 still wants the loads you will run at one time. Do not add generator 1.25 here. Do not add inverter 1.25 here. Autonomy days already scale energy. Extra percentages belong on a datasheet you can quote.
Round-trip efficiency on a pack sheet is not always the same as inverter efficiency. Type the fraction that matches the boundary you care about. If you already derated on the solar panel page with 0.86, do not stack another silent 0.86 here. Each eta field is local to its page.
Lead-acid often lists 50 percent DoD for cycle life. That is a product choice. Type 0.5 and the default day becomes 24 kWh. Lithium often lists a higher usable fraction. Type the sheet. This engine will not pick a chemistry for you.
Temperature cuts capacity. A sheet may say 80 percent at 0 °C. That is another typed fraction, not a hidden winter table. If you lack a sheet, leave eta and DoD at 1 and say the rating is nameplate at the stated temperature.
Common questions
What size solar battery do I need for 12 kWh per day?
12 kWh of rated storage for one day at depth 1 and efficiency 1. More kilowatt-hours if you type more days or a smaller usable fraction.
Why not default 80 percent?
Because 80 percent is a common lithium marketing number, not a cited default for every chemistry. Battery size on this site already starts at 1. This page matches that.
How is this different from battery size?
Battery size returns amp-hours at a typed voltage. This page returns kilowatt-hours. Same energy idea, different unit.
Does this include the solar array?
No. Array kilowatts are daily energy divided by peak sun hours on the solar panel page. Storage is a separate product. You can need both.
Limitations
This is a calculation aid, not a permit.
Battery size starts at 1000 W times this daily energy in hours, 12 volts, and the same depth and efficiency. That keeps energy matched in watt-hours.
It does not default 80 percent DoD. It does not default 90 percent efficiency. It does not pick lithium or lead-acid. It does not size a charge controller. It does not apply NEC 480. It does not convert to amp-hours until you open battery size. It does not store what you type. Search engines should use the clean address of this tool. It is not a permit. Temperature, cycle life, and BMS limits still live on the pack sheet.
The address of a filled-in calculation includes energy, days, depth, and efficiency. A filled-in address points its canonical link at the page with no query. Keep the assumptions with the kilowatt-hours. The print button hides the menu and the form. The steps stay. Rated kWh is a planning floor, not a brand and not an 80 percent guess.
Peukert's law for lead-acid says high current delivers fewer amp-hours than the 20 hour rating. This kWh page does not apply Peukert. If you have a 20 hour rating and a high current, use the amp-hour page with a typed efficiency below 1, or stay on nameplate kWh and say so. Do not hide Peukert inside an 80 percent DoD default.
Grid-tied batteries with a backup gateway are still rated in kilowatt-hours. Days of autonomy still multiply. The difference is whether the array can refill the bank the next day. That refill is solar panel size, not this card. If the array is too small, extra days of storage only delay an empty pack. Size both.
Usable kilowatt-hours on a carton are sometimes already derated. If the carton says 10 kWh usable from a 13.5 kWh pack, that is a printed DoD. Type daily energy against the usable number and leave DoD at 1, or type rated energy and the printed fraction. Do not apply 0.8 on top of a carton that already printed usable energy. 13.5 and 10 here are an example of how to read a sheet, not a default pack this engine sells.
Sources
- U.S. Department of Energy Federal Energy Management Program, Battery Energy Storage System Evaluation Method. Accessed 2026-10-17.
- NIST Special Publication 330, The International System of Units (SI), Section 2. Accessed 2026-10-14.
- Virginia Cooperative Extension ENERGY SERIES: Estimating Appliance and Home Electronic Energy Use. Accessed 2026-10-19.
Storage = daily kWh × days / (DoD × η) is a conditional sizing calculation. The 12 kWh default is illustrative; it is not a Virginia Tech appliance rating or typical household load. No 80 percent DoD is stored in the engine.
Virginia Cooperative Extension lists a toaster-oven example at 1,225 W. At 8 hours, that example is 9.8 kWh before any storage losses; actual appliances vary, so use your own measured daily energy rather than this category example.
Cite this page
Wattopedia Editorial Team. Solar battery size. https://wattopedia.com/solar-battery-size-calculator . Updated 2026-10-29.