kVA to Amps Calculator (AC, DC, 3-Phase)

Convert apparent power in kVA to current using voltage and phase count.

Circuit

1.5 kilovolt-amperes at 120 volts, single-phase, draws 12.5 amps. For single-phase AC, apparent power is RMS volts times RMS amps. Power factor is not an extra divisor in this formula.

CurrentAMPS
12.5 A

Calculated current

Show steps
Kilovolt-amperes
1.5 kVA
Volts
120 V
Circuit
Single-phase AC
  1. Circuit is single-phase AC.
  2. Volt-amperes = 1.5 × 1000 = 1500 VA.
  3. Current = 1500 / 120 = 12.5 A.
  4. Power factor is not used. Kilovolt-amperes are apparent power.

Estimate only. Check equipment labels and local code.

How the number is made

How to use this calculator

  1. Type the kilovolt-amperes and the volts.
  2. Choose DC, single-phase AC, or balanced three-phase AC.
  3. For AC, apparent power uses RMS voltage and current; power factor is not an extra divisor when apparent power is already known.
  4. The amps appear in the result card with the calculation steps.
  5. Submit the form if JavaScript is off.

One kilovolt-ampere is 1000 volt-amperes. The first step always makes that product. Then the current is volt-amperes divided by volts on DC and on single-phase, or divided by the square root of 3 times volts on three-phase. Use this page for a transformer, a UPS, or a generator that lists kVA. If the label lists kW, use kW to amps instead.

Use line-to-line volts for three-phase. A 208 V three-phase panel is the voltage between two hot wires. This page does not convert 120 V to 208 V for you.

Formula

First: S = kVA × 1000

S=kVA×1000

For AC, S is apparent power in volt-amperes, V is RMS volts, and I is RMS amps. The DOE Electrical Science handbook defines S as RMS voltage times RMS current. The DOE-reproduced motor-systems guide gives the three-phase apparent-power relationship using line-to-line voltage and line current. This page rearranges those equations to solve for current; it is not a conductor or installation-sizing rule. For DC, the input is treated as a volts-times-amps power value, not as AC apparent power.

Why there is no power factor

Power factor relates real power to apparent power on AC. This page already starts from apparent power, so dividing by power factor again would apply the wrong relationship. Omitting that extra divisor is part of the stated equation, not an equipment safety margin.

If you have kilowatts and a power factor, do not invent a kVA by guessing. Use the kW page with that factor. If you have only kVA, stay on this page.

DC

DC and single-phase: I = S / V

I=SV

Direct current has no reactive power in the AC sense. Volts times amps is the power. Typing kVA on DC is the same arithmetic as typing kW. The engine still accepts the DC choice so a shared address can record that the circuit was DC. The steps state that kilovolt-amperes and kilowatts are the same product on DC.

A DC battery inverter that lists kVA on the AC side is not a DC kVA figure. Type the AC volts with that kVA, and choose single-phase or three-phase to match the output, not DC.

Single-phase AC

DC and single-phase: I = S / V

I=SV

For single-phase AC, current is apparent power divided by RMS voltage. A hypothetical 1.5 kVA load at 120 V gives 12.5 A; a separate 1.5 kVA example at 240 V gives 6.25 A. These scenarios do not establish that one transformer or UPS supports both voltages or operating points.

If equipment lists both kVA and kW limits, keep the apparent-power and real-power ratings distinct and read their stated operating conditions. Neither rating by itself selects conductors, establishes runtime or determines another device's suitability.

Three-phase AC

Three-phase: I = S / (√3 × V)

I=S3×V

Three-phase current is lower than single-phase current for the same kVA and volts, because the square root of 3 is in the denominator. The volts have to be line to line. If you type the phase-to-neutral voltage by mistake, the amps come out high. Type the voltage printed on the transformer as line to line when that is what the nameplate means.

A three-phase transformer lists kVA as a three-phase rating. Do not divide that kVA by three and then run this page three times as single-phase unless you know you are looking at a bank of single-phase units. The three-phase choice already spreads the rating across the three legs.

Worked example

  1. Type 5 kilovolt-amperes, 240 volts, single-phase.
  2. The engine returns 20.8333 amps.
  3. The steps are 5 times 1000, then 5000 divided by 240.
  4. Power factor is not used.
  5. Change the circuit to three-phase and type the line-to-line voltage if that is the system you have. The reference table below is the same engine, single-phase, for a set of round kVA values at 120 V and 240 V. It is not a list of transformer catalog numbers.

Amps at 120 V and 240 V

Single-phase. Every cell is computed by the same function as the result card.

Kilovolt-amperesAmps at 120 VAmps at 240 V
0.5 4.1667 2.0833
1 8.3333 4.1667
1.5 12.5 6.25
2 16.6667 8.3333
3 25 12.5
5 41.6667 20.8333
7.5 62.5 31.25
10 83.3333 41.6667

Transformers, UPS units, and generators

For a stated apparent power and voltage, the current calculation does not need power factor. For three-phase AC, use total apparent power, RMS line-to-line voltage and a balanced-load assumption. The result is line current under those conditions, not a product selection or an assessment of equipment capability.

The bound DOE Electrical Science reference supplies the RMS apparent-power relationship. The bound Energy Management for Motor-Driven Systems guide supplies the three-phase line-voltage and line-current relationship. These references support the equations, not conductor, breaker, transformer, UPS or generator selection.

Server-rendered results use the values in the request URL. Shared addresses may remain in browser history and server logs. Do not enter confidential information.

Common questions

How do I convert kVA to amps?

Multiply kilovolt-amperes by 1000, then divide by volts for DC or single-phase. For three-phase, divide by the square root of 3 times the line-to-line volts. Do not divide by a power factor.

Why is there no power factor on this page?

For AC, kilovolt-amperes are apparent power, so current follows from the AC apparent-power formula. A power factor converts between apparent and real power; this calculator already starts from apparent power and does not apply it again.

Is kVA the same as kW on DC?

As a product of volts and amps, yes. The steps say so. On AC they match only when the power factor is 1.

How do I convert kVA to amps for three-phase?

Convert kVA to volt-amperes, then divide by the square root of 3 times the line-to-line volts. Do not use the single-phase formula on a three-phase transformer.

Does this determine a wire size?

This page does not determine conductor size or overcurrent protection. Its optional DC link is a voltage-drop estimate only; do not use it for AC or ampacity decisions.

Limitations

This is a calculation aid, not a permit.

For DC only, the optional link carries volts and calculated amps into a voltage-drop estimate. Its length and drop target are separate inputs. It does not select conductors or protective devices, and AC results are not carried into that estimate.

Model: steady DC or sinusoidal AC. AC values are RMS; three-phase requires a balanced load, total apparent power, line-to-line voltage and line current. Power factor is not an extra divisor for a stated apparent-power input. Unbalanced loads and distorted waveforms are outside this model. This is arithmetic, not equipment or installation selection.

It does not convert kVA to kW. That step needs a power factor, and this form will not guess one. It does not pick a conductor, breaker, or transformer size from a house load list. For DC only, the optional next link opens an idealized copper voltage-drop estimate; that estimate does not check ampacity or determine a safe installation size. AC conductor design needs a qualified review using applicable requirements. The values stay in the page address; search engines should use the clean address.

The address of a filled-in calculation includes the kilovolt-amperes, the volts, and the circuit. There is no power-factor query. That is useful when you send the working to someone else. Search engines should use the clean address of this tool. A filled-in address points its canonical link at the page with no query. The number on the card is the same either way, because the server computes it before any script runs.

Results are rounded to four decimal places. For single-phase AC, 1.5 kVA at 120 volts is 12.5 amps. The table uses the same rounding. These are reproducible arithmetic examples, not measurements or circuit-design results.

Keep the assumptions with the number. A current without the kVA, the voltage, and the circuit cannot be checked later. Show steps includes those three items so a printed page still shows them. The print button hides the menu and the form. The steps stay.

Sources

  1. U.S. Department of Energy Fundamentals Handbook, Electrical Science, Volume 3. Accessed 2026-10-29.
  2. Energy Management for Motor-Driven Systems, Revision 2. Accessed 2026-10-29.

Cite this page

Wattopedia Editorial Team. kVA to Amps Calculator (AC, DC, 3-Phase). https://wattopedia.com/kva-to-amps . Updated 2026-10-28.