UPS runtime calculator

Estimate UPS battery runtime from amp-hours, voltage, load and loss factors.

A 100 amp-hour 12 volt UPS battery stores 1200 watt-hours. At 50 watts, depth of discharge 1, and efficiency 1, runtime is 24 hours.

RuntimeUPS
24 h

Runtime

Show steps
Amp-hours
100 Ah
Volts
12 V
Load
50 W
Depth of discharge
1
Efficiency
1
  1. Nominal energy is amp-hours times nominal volts; usable energy needs the stated discharge and efficiency assumptions.
  2. Energy = 100 × 12 = 1200 Wh.
  3. Usable = 1200 × 1 × 1 = 1200 Wh.
  4. Runtime = 1200 / 50 = 24 h.

Estimate only. Check equipment labels and local code.

Runtime = Ah × V × DoD × η ÷ W

How to use this calculator

  1. Type amp-hours, volts, load watts, depth of discharge, and efficiency.
  2. The card shows runtime in hours.
  3. The same formula runs on the server, so the first number is already on the page.

Formula

h = Ah × V × DoD × η ÷ W

Amp-hours, volts, and load must be greater than zero. Depth of discharge and efficiency must be from 0 to 1. This is a planning estimate, not a UPS specification.

Runtime at different loads

WattsHours
10 120
25 48
50 24
100 12
150 8
200 6
500 2.4

Limitations

This is a calculation aid, not a permit.

Battery runtime

Default is a 100 amp-hour 12 volt UPS battery at a 50 watt load, full depth of discharge, and efficiency 1.

Sources

  1. U.S. Department of Energy Federal Energy Management Program, Battery Energy Storage System Evaluation Method. Accessed 2026-10-17.
  2. NIST Guide to the SI, SP 811, Appendix B.8: conversion factors. Accessed 2026-10-14.
  3. NIST Special Publication 330, The International System of Units (SI), Section 2. Accessed 2026-10-14.
  4. Victron BMV-700 manual: battery capacity and Peukert exponent. Accessed 2026-10-14.

Cite this page

Wattopedia Editorial Team. UPS runtime calculator. https://wattopedia.com/ups-runtime-calculator . Updated 2026-10-29.