kva to amps chart

This kVA to amps chart gives line current for a balanced three-phase load. Each voltage is line to line. The figures use apparent power, so power factor is not an input.

You can also use your browser’s Print command.

kva to amps chart data table
Apparent power kVA Line A at 208 VLL, balanced 3-phase Line A at 400 VLL, balanced 3-phase Line A at 480 VLL, balanced 3-phase
1 2.7757 1.4434 1.2028
5 13.8786 7.2169 6.0141
10 27.7572 14.4338 12.0281
15 41.6358 21.6506 18.0422
25 69.3931 36.0844 30.0703
50 138.7861 72.1688 60.1407
75 208.1792 108.2532 90.211
100 277.5722 144.3376 120.2813
250 693.9306 360.8439 300.7033
500 1387.8612 721.6878 601.4065
1000 2775.7224 1443.3757 1202.8131

How to read it

Select the apparent-power row and the stated line-to-line voltage. The calculation first converts kilovolt-amperes to volt-amperes, then divides by the product of line voltage and the square root of three. The answer is line current under the balanced-load assumption. Line-to-neutral voltage is not interchangeable with the column heading. A balanced system has matching phase conditions; this lookup does not solve an arbitrary unbalanced combination of loads.

What this chart is not

Apparent power and real power answer different questions. Do not substitute a real-kilowatt figure into a kVA row or multiply by power factor again when calculating current from a known apparent-power value. Nor should a transformer's stated capacity be mistaken for the amount it is currently supplying. The table does not establish transformer suitability, motor full-load code current, startup allowance, protective-device selection or conductor ampacity. Those require their own equipment and installation information.

Print and next step

Keep the balanced-load and line-voltage qualifiers visible with a saved copy. For a different supply voltage or a single-phase case, use the kVA-to-amps calculator with the proper circuit choice. The printed values are rounded current estimates from the cited electrical model, not measurements. If the source data does not say whether voltage is line to line or line to neutral, establish that distinction before interpreting the result.