Single phase motor current formula

This single phase motor current formula chart estimates current from motor horsepower and voltage. It also needs motor efficiency and power factor. The chart shows a coefficient, not a final current reading. Divide that value by efficiency times power factor to estimate amps. It is not a code table or wiring approval.

You can also use your browser’s Print command.

Single phase motor current formula data table
Rated output hp Mechanical output W A coefficient at 115 V A coefficient at 230 V
0.25 186.4 1.621 0.811
0.5 372.8 3.242 1.621
0.75 559.3 4.863 2.432
1 745.7 6.484 3.242
1.5 1118.5 9.727 4.863
2 1491.4 12.969 6.484
3 2237.1 19.453 9.727
5 3728.5 32.422 16.211

How to read the coefficients

Each row starts with rated mechanical horsepower and its equivalent shaft output in watts. The two coefficient columns divide that output by the listed voltage. To estimate running current, use I = coefficient / (efficiency × power factor). Enter efficiency and power factor as decimal fractions from the motor data, not as whole-number percentages. A fraction such as eighty-five percent must first be converted to its decimal form. The one-horsepower row shows 745.7 watts of mechanical output. Its 115-volt coefficient is 6.484 amps, before the efficiency and power-factor adjustment. Its 230-volt coefficient is 3.242 amps before that adjustment. Both inputs must be known and greater than zero for the estimate to be meaningful. Do not treat a blank motor rating as a valid input. The printed coefficients are rounded, so a calculation from the exact conversion factor may differ slightly in the last digit. Use unrounded values when doing a separate calculation.

What this estimate does not tell you

Horsepower describes mechanical output, not the electrical input by itself. Motor losses mean input power is higher than shaft output. Power factor also changes the relationship between real power and current. That is why the formula needs both efficiency and power factor from the actual motor. If either value is unknown, the chart cannot give a reliable motor-specific current estimate. It does not contain manufacturer nameplate readings, starting current, service-factor behavior, or a code table. It is not NEC full-load current, branch-circuit conductor ampacity, overload protection, or breaker sizing. Do not use this estimate to select conductors or protective devices. For an installation, follow the motor nameplate, equipment instructions, locally adopted electrical rules, and a qualified professional's review. The Department of Energy references support the power and efficiency relationships used here; the values in this chart are calculated independently.

A safe way to use the estimate

First read the motor nameplate and confirm its rated horsepower, voltage, phase, efficiency, and power factor. This chart only covers single-phase examples at 115 and 230 volts. A different voltage is not represented by either column. Then select the matching horsepower row, divide the coefficient by the efficiency and power factor, and keep the result as an estimate for comparison. A measured operating current can differ with load, supply conditions, motor design, and measurement method. If the nameplate already states amperes, use that rating for the purpose specified by the manufacturer rather than replacing it with a generic calculation. The chart's output-watt column describes mechanical shaft output; it is not a promise about input watts or energy use. For a separate load conversion, use the watts-to-amps calculator with the correct real input power and power factor. The chart library contains other references, and the contact page accepts data corrections.